Skip to main content

SP POWERWORLD ADVR-08

Analog-Digital Hybrid 2 lines sensing 8Amp AVR with multiple power input capability

The Universal ADVR-08 Generator Automatic Voltage Regulator can accept multiple power input such as SHUNT, AUX, Harmanic, and PMG. I

Ex stock - shipped Worldwide. For GBP, EURO or USD pricing please contact us:

Sales: james.daff@sp-powerworld.com

Office: info@sp-powerworld.com

Tel: +44 (0)115 923 2568 (United Kingdom)

Tel: (24-hour) +44 (0)7484709956 (United Kingdom)

*All manufacturer names, numbers, symbols and descriptions are used for reference purpose only and do not imply that any part is the product of these manufacturers.

Manual

Features

  • Power input 1 phase 40-300 Vac @ 50-500 Hz
  • Sensing input 1 phase 110-480 Vac selectable
  • Voltage regulation * 50 Hz / 60 Hz selectable
  • Multiple power input source SHUNT, AUX, HARMONIC, PMG
  • Inverse-time over excitation & under frequency protection
  • Soft start voltage ramping
  • Built-in high capacity protection fuse

Specifications

• Sensing Input Voltage : 110-480 Vac 1 phase selectable Frequency : 50 Hz / 60 Hz selectable
• Power Input Voltage : 40-300 Vac single phase Frequency : 50-500 Hz
• Aux. Input Voltage : 40-300 Vac single phase Frequency : 50-500 Hz
• Output Voltage : Max. 63 Vdc @ power input 110 Vac Max. 125 Vdc @ power input 220 Vac Current : Continuous 8A, Intermittent 12A for 10 sec. Resistance : ≧ 8 ohms @ power input 110 Vac ≧ 16 ohms @ power input 220 Vac Fuse Spec. : 5 x 20 mm S505-10A (slow blow type)
• Burden in Shunt & PMG Wiring 880 VA @ power input 110 Vac 1760 VA @ power input 220 Vac
• Volts Regulation • Build Up Voltage Residual volts at AVR power input terminal > 6 Vac @ 25 Hz
• Over Excitation Protection Inverse-time 125 +/- 5 Vdc @ power input 220 Vac
• External Volts Adjustment +/- 5% 500 ohms 1 watt potentiometer +/- 10% 1000 ohms 1 watt potentiometer
• Unit Power Dissipation Max. 6 watts
• EMI Suppression Internal EMI filtering Soft Start Ramp Time 4 sec.
• Voltage Thermal Drift 0.03% per °C change in AVR ambient.
• Analogue Input Un 0-10% @ 0-1 Vdc or +/- 5 Vdc.
• Quadrature Droop Input CT 1A / 5A Max. +/- 5% @ P.F +/- 0.7 Under Frequency Protection (Factory Knee Point Setting) 50 Hz system presets knee point at 47 Hz 60 Hz system presets knee point at 57 Hz (-40 - +70 °C deviation 0.1 Hz)
• Environment Operation Temperature : -40 - +70 °C Storage Temperature : -40 - +85 °C Relative Humidity : 95% (max.) Vibration : 3Gs @ 100-2K Hz
• AVR Controls Function VOLT : Voltage adjustment STAB : Stability adjustment U/F : Setting under frequency protection knee point DROOP : Current compensation droop adjustment TRIM : Analogue input adjustment DIP : Voltage droop ratio setting
• Indication LED O/E LED : Over excitation protection indicator U/F LED : Under frequency protection indicator
• Dimension 171.0 (L) x 120.0 (W) x 50.0 (H) mm
• Weight 820 g +/- 2%

Dimensions