SP POWERWORLD ADVR-12
Universal Automatic / Digital Voltage Regulator
The SP Powerworld ADVR-12 12 Amp Universal Automatic / Digital Voltage Regulator is a Compatible Replacement for the Caterpillar 3516 - VR6 - VR3 - CDVR - K125-10B - K65-12B. Marelli M40FA640A/A. Basler DECS-100 - AVC63-12A - Digital DM110 - KR4FF. Marathon DVR2000 - DVR2000E - PM100 - PM200 - PM300.
Ex stock - shipped Worldwide. For GBP, EURO or USD pricing please contact us:
Sales: james.daff@sp-powerworld.com
Office: info@sp-powerworld.com
Tel: +44 (0)115 923 2568 (United Kingdom)
Tel: (24-hour) +44 (0)7484709956 (United Kingdom)
Features
- Single phase sensing & single phase and three phase power input
- Voltage regulation < ±0.5%
- 220/380/440/480VAC programmable input
- DIP switch selectable 50/60Hz
- Multiple excitation system compatibility: SHUNT, AUX, PMG
- Inverse-time over excitation protection
- Under frequency protection
- Soft start voltage ramping
- EMI suppression
- Built-in high capacity protection fuse
Specifications
Sensing Input | Voltage 180~520VAC single phase DIP switch selectable Frequency 50/60Hz jumper selectable |
---|---|
Power Input | Voltage 100~300 VAC single phase or three phase |
Output | Voltage Max. 125VDC @ 220VAC Current Continuous 12A, Intermittent 25A for 10 Sec. |
Volts Regulation | < ±0.5% (with 4% engine governing) |
Voltage Build-up | Residual volts at AVR terminal > 6VAC |
Over Excitation Protection | Inverse-time 125±5VDC @ 220VAC |
External Volts Adjustment | 10 K Ohm 1 watt trimmer |
Unit Power Dissipation | Max. 8 watt |
Soft Start Ramp Time | 4 Sec. |
EMI Suppression | Internal electromagnetic interference filtering |
Thermal Drift | 0.03% per °C change in AVR ambient |
Under Frequency Protection (Factory Setting) |
60Hz system presets knee point at 55Hz 50Hz system presets knee point at 45Hz |
Environment | Operating Temperature : -40~70 °C Storage Temperature : -40~85 °C Relative Humidity : Maximum 95% Vibration : 3G @ 100~2KHz |
AVR Controls Function | VOLT : Voltage Adjustment STAB : Stability Adjustment U/F: To Set the U/F Knee Point (*U/F: Under Frequency Protection) DROOP : Droop Adjustment TRIM : Analogue Input Adjustment DIP : U/V Rate Set O/E LED : O/E Protection Indicator (*O/E : Over Excitation Protection) U/F LED : U/F Protection Indicator |
Dimensions | 214.0 (L) x 163.0 (W) x 45.7 (H) mm |
Weight | 1130g ±2% |